Use the tool below to estimate the UPS (uninterruptible power supply) or voltage regulator capacity needed for a home, office or workshop. Select the usage area and the solution you want to size, specify the electrical system (single/three phase and voltage), pick the devices; the tool calculates the required kVA, W and, for a UPS, the Wh energy need including a start-up (surge) margin.
Mentor CNC UPS and Voltage Regulator Calculator
Select the devices to be used in a home, office or workshop. The tool sizes the UPS and the voltage regulator with different methods and shows you a simple capacity result.
1. Select the usage area and calculation type
2. Select the electrical system
3. Select the devices to be used
4. Enter the final details
Advanced settings — for technical users
Difference between a UPS and a voltage regulator
A UPS keeps devices running from its battery for a set time during a power cut, so both power (kVA/W) and energy (Wh) are calculated. A voltage regulator does not keep the power on during an outage; it only protects devices by stabilizing incoming low or high grid voltage, so only power (kVA) is calculated. This tool supports both solutions; depending on the chosen solution, the relevant fields (runtime, battery ratio, etc.) come into play.
The total Watt value of the devices is divided by the power factor to find the apparent power (VA/kVA): kVA = W / (power factor × 1000). The approximate line current is I = VA / Volt on single phase and I = VA / (√3 × Volt) on three phase. Because motor devices (refrigerator, compressor, pump, CNC, press) draw several times their normal power at start-up, the tool adds the highest start-up (surge) margin separately and rounds the safe capacity up to a practical standard value.
How to use the results
The calculated values are for pre-sizing and do not recommend any brand or product. When choosing a system, evaluate a device that meets both the required kVA/W capacity and, for a UPS, the Wh energy value. For critical, medical or high-power industrial systems (for example CNC machines), the device label values, the real start-up currents and a qualified electrical engineer’s assessment must be the basis.
W, VA and kVA: which number describes what?
W (watts) is active power — the power actually converted into work and heat. VA (volt-amperes) is apparent power — the product of voltage and current, which is what the cabling, the transformer and the UPS output stage must physically carry. The ratio between them is the power factor: PF = W / VA.
A UPS nameplate normally carries both limits, for example “3000 VA / 2700 W”. The unit is suitable only when the load stays below both. A load of 2500 W at a power factor of 0.7 draws 3571 VA — within the watt limit but well over the VA limit, and the UPS will overload.
| Quantity | Formula | Note |
|---|---|---|
| Power factor | PF = W / VA | Between 0 and 1 |
| Single phase | S = V × I | V is line-to-neutral, typically 230 V |
| Three phase | S = √3 × V × I | V is line-to-line, typically 400 V |
| Motor input | S = Pshaft / (η × PF) | Nameplate kW is shaft power |
| Energy | Wh = W × (minutes / 60) | Determines runtime, not VA |
Three-phase installations: where the calculation usually goes wrong
In a three-phase workshop the apparent power is S = √3 × V × I, and V here is the line-to-line voltage — 400 V, not 230 V. Substituting 230 V produces a result about 43% too low. A 32 A three-phase supply is √3 × 400 × 32 ≈ 22.2 kVA, not 12.7 kVA.
A second point is load balance. Single-phase loads distributed unevenly across the three phases make one phase carry considerably more current than the others. A three-phase UPS is sized for the most heavily loaded phase, not for the average. When a large single-phase load is unavoidable, a 3/1 configuration — three-phase input, single-phase output — spreads the draw more evenly across the supply.
Inrush current: what really breaks the sizing
Motors, compressors, hydraulic units and pumps draw three to seven times their rated current for a fraction of a second when starting. A UPS that cannot supply this brief pulse raises an overload alarm and transfers to bypass — exactly at the moment protection was needed.
Allow for the starting surge of the largest single motor rather than summing the inrush of every motor, because in practice they do not start simultaneously. Where several must start together, a soft starter or a variable frequency drive reduces the surge and often removes the need for a much larger UPS.
Separately, IT loads bring the opposite problem: switch-mode power supplies draw current in short peaks rather than as a sine wave, so a UPS intended for computers and servers should have a crest factor of at least 3:1.
UPS topologies under IEC 62040-3: VFD, VI and VFI
Commercial names differ between manufacturers, but IEC 62040-3 classifies every UPS by how far its output depends on the input supply. This three-letter code is the figure to compare in a quotation.
| Class | Meaning | Common name | Transfer time | Typical use |
|---|---|---|---|---|
| VFD | Output depends on input voltage and frequency | Offline / standby | ~4–8 ms | Home computers, modems, small non-critical loads |
| VI | Voltage independent, frequency dependent | Line-interactive | Short | Offices, NVRs, network gear, small servers |
| VFI | Voltage and frequency independent | Online (double conversion) | No break (0 ms) | Servers, data centres, CNC controls, industrial PCs |
A voltage regulator is not a UPS. It corrects voltage while the mains is present, but without stored energy it supplies nothing during an outage. A VFI unit, by contrast, feeds the load through AC → DC → AC double conversion at all times and takes energy from the battery the instant the supply fails. Where the mains is present but poor, a regulator can be enough; where an outage must not stop the process, only a UPS with storage will do.
Power quality and CNC machines
Resistance spot welders, arc welders and large motors are rapidly varying high-power loads. Their current pulses create a voltage drop across the supply and installation impedance, producing voltage dips and, when repeated, flicker at the common coupling point. The severity depends not only on the total kW but on the magnitude and duration of the change, the short-circuit power of the shared supply and the cable and transformer impedance.
If the CNC control transformer or switch-mode supply falls below tolerance, the 24 V DC control bus can dip with it. PLCs, I/O modules, contactors, relays, encoders and drive control stages may alarm, reset or lose communication. This is a loss of secondary voltage regulation or the DC bus falling below its minimum threshold — not a fault in the transformer itself.
How a vertical Z axis behaves during an outage is machine-specific: servo brakes, counterweights, balancing systems and safe-stop functions all differ. A UPS does not replace a mechanical brake or a safety circuit, and axis movement must follow the machine builder approved procedure.
Powering an entire CNC machine from a UPS is not a simple sum of kW. Spindle and servo peak currents, regenerative energy returned by decelerating axes, harmonics, crest factor, bypass behaviour, generator compatibility and the emergency-stop architecture all have to be assessed. In many machines the more sensible approach is to back up only the control unit, the industrial PC and the 24 V rail, giving the operator a controlled shutdown rather than continued machining.
Worked example: a small machine shop
A workshop wants a controlled shutdown, not continued production, for 15 minutes after a power failure.
| Load | Qty | Unit | Total |
|---|---|---|---|
| CNC control unit + industrial PC | 2 | 350 W | 700 W |
| Office PC and monitor | 2 | 240 W | 480 W |
| Server | 1 | 600 W | 600 W |
| Network, NVR, modem | 1 | 100 W | 100 W |
| Total | 1880 W | ||
- Power margin: 1880 × 1.25 = 2350 W.
- Apparent power at PF 0.8: 2350 / 0.8 ≈ 2938 VA → 3 kVA standard class.
- Energy for 15 min: 1880 × 0.25 = 470 Wh.
- Losses and margin: 470 / 0.88 × 1.20 ≈ 641 Wh; with an ageing factor of 1.25 ≈ 801 Wh.
- On a 48 V bus: 801 / 48 ≈ 17 Ah, so four 12 V batteries of 18–24 Ah in series.
Result: a 3 kVA VFI (online) UPS with a 48 V battery bus. The spindle and axis drives stay outside the UPS; only the control, the PC and the 24 V rail are backed up.